Turbo Generator(TG) Specification 210 MW

Rated MVA rating MCR conditon- 247 MW
Rated KVA rating MCR conditon- 210 MW
Terminal Output Voltage- 15.75KV



Rated Current- 9050 A
Power Factor- 0.85 Lagging
Excitation Voltage- 310 V DC
Excitation Current- 2600 A
Stator Phase Connection- Star_Star
Rated Frequency- 50 Hz
Rated Speed- 3000 RPM
Cooling System- Stator_water (H2O)
Rotor_Hydrogen (H2)
Gas Pressure- 3.5 Kg/Cm
Type Of Insulation- Class B
No Of Terminal Brought Out- 9
Rotation Of Rotor- Anticlockwise(View on Slip ring end)

Over All Stator Dia- 3960 MM
Length Of Stator- 4580 MM
Weight Of Stator- 175,00 Kg

Length Of Rotor- 9770 MM
Weight Of Rotor- 42,200 KG

Types of Loss in Power System / Energy losses

There are many types of losses in transmission line  as follow... 1. Resestive loss 2. Inductive loss 3. Radiation loss 4. Eddy curren...